H07 BQ-F

ENERGY TRANSMISSION ELASTOMERIC EI6 INSULATED CABLES WITH POLYURETHANE SHEATH
SUITABLE IN DRY, HUMID OR MOIST SITUATIONS, EVEN ON IMMERSION

Accordingly to the standards BT 2006/95/CE

CENELEC HD516 S2

A

Flexible red copper conductor.

B

Elastomeric mixture Insulation in EI6 quality.

C

Polyurethane sheath.

NOMINAL VOLTAGE Uo/U:

450 / 720 v

MAXIMUM OPERATING TEMPERATURE:

+90°C

MAXIMUM SHORT CIRCUIT TEMPERATURE:

+250°C

(OIL RESISTANT HD505.2.1)

 

Main features:

In dry, humid or moist situations, outdoors (AD6 and AD7); for medium mechanical stresses, such as: equipments in industrial and agricultural workshop, heating installations where there is no risk of contact with hot parts and is not subject to radiations, electric tools as drills, circular saws, motors or transportable generators in construction sites or agricultural plants and so on, for use in cold-storage applications. Especially suitable in situations where the cable is  subject to high abrasion and tear stresses. Suitable for permanent outdoor use where a black sheath is specified and tested against appropriate requirements, or the manufacturer has provided suitable alternative protections.

Maximum Voltage:

A system operational voltage can always overflow the 10% of its standard voltage.

Employment:

Minimum installation and use temperature: -40C
Minimum bending radius per D cable diameter in mm:

 

Fixed Lays Cables

D<8

8<D<12

12<D<20

D>20

 

Normal Use

4D

5D

6D

6D

 

Accurate Bending close to the terminal

2D

3D

4D

4D

Flexible cables

 

 

 

 

 

Fixed Lay

3D

3D

4D

4D

 

Free Move

4D

4D

5D

6D

 

At the entrance to a portabe device or a mobile equipment:

 

 

 

 

 

·         Without cable stressing

4D

4D

5D

6D

 

·         With mechanical stress

6D

6D

6D

8D

 

Festoon i.e. for support crane

6D

6D

6D

8D

 

Repeated wiring

6D

6D

6D

8D

 

Turned off on pulley

8D

8D

8D

8D

 

Packaging:

100mt. rings in thermoplastic film or drums to agree.
NOTE: Maximum storage temperature: +40°C

Core colours:

Single core: black; Two cores: blue-brown;
Three cores: brown-black-gray (or blue-brown-Y/G);
Four cores: blue-brown-black-gray (or Y/G instead blue);
Five cores: Y/G-blue-brown-black-gray (or black instead Y/G);
Multicores: black with numbers.

Sheath colour: Orange.

 Ink marking: <HAR> - H07 BQ-F - year

Or according to customer’s requirements.

 

Cores number[N ]

Cross section [mm²]

Approx  conductor diameter [mm]

Insulation medium thickness [mm]

Approx production diameter [mm]

Approx cable weight [kg/km]

Electric resistance at 20C    [Ohm/km]

RedCu  Tinned Cu 

Current  carrying capacities amb. temp.
mobile service
[A][A]

2x

1.5

1.6

0.8

8.51

95

13.7

13.3

20

2.5

2.0

0.9

10.01

137

8.21

7.98

26

4

2.6

1.0

11.61

193

5.09

4.95

35